Abstract:This paper compares five observed variables for the parameter identification of generators, i.e. the relative rotor angle between the generators, the relative phase angle of generator port voltage, the active powers through the tie-lines, the reactive powers through the tie-lines and the voltages at the key buses. The comparative results of trajectory sensitivity phase show that the generator parameters may be identifiable with an observed variable but unidentifiable with another variable. The comparative results of trajectory sensitivity magnitude indicate that the relative rotor angle behaviors the largest sensitivity, and then the relative phase angle of generator port voltage, the active powers through the tie-lines, the reactive powers through the tie-lines and the voltages at the key buses sequentially. The comparative results of parameter estimation precision show that the best one is the relative rotor angle. Therefore, the variables with no in-phase and large sensitivity could be selected.