Experimental study on heat and mass transfer characteristics in evaporative cooler with ceramic foam packings

Geng Wang,Xiaosong Zhang,Yao Chen,Guoying Xu
DOI: https://doi.org/10.3969/j.issn.1001-0505.2012.03.012
2012-01-01
Abstract:Alumina (Al 2O 3) ceramic foam blocks with a pore density of 30 PPI (pores per inch) were selected to be the direct evaporative cooling experimental wetted pad. Experiments were carried out in a psychrometric chamber with controllable air temperature and humidity. The effects of operating parameters, such as height of the packing, the dry-and wet-bulb temperature of inlet air, as well as mass flow ratio of water to air, on the heat and mass transfer performances were analyzed. Cooling efficiency and the humidity increment were chosen as the performance index. Experimental results show that a cooling efficiency of 0.88 and a water content increment of 3.15 g/kg can be achieved. The cooling efficiency of the packing decreases with the increasing inlet air dry-and wet-bulb temperature and the air flow rate. The water content increment rises with the increment of the inlet air dry-bulb temperature, but drops with wet-bulb temperature and the air flow rate. Both the cooling efficiency and the water content increment grow with the height of the packing.
What problem does this paper attempt to address?