Variation of AC Corona Discharge Pulse Characteristics with Air Pressure and Humidity

孟晓波,惠建峰,卞星明,陈枫林,王黎明,关志成
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2011.28.018
2011-01-01
Abstract:Corona problem at high altitude has attracted more and more attention from investigators as UHV AC and DC transmission lines is being constructed. In the chamber made of organic glass for adjusting pressure and humidity, it was studied that the variation of ac corona characteristics with air pressure and humidity through rod plane electrodes. It was found through experiments that the inception voltage of AC corona was reduced as pressure decreased or humidity increased. Furthermore, the average amplitude of AC corona pulse decreased with rise of humidity or fall of air pressure. The average amplitude of AC corona pulse in the positive half-cycle decreased as air pressure reduced, however, average amplitude of AC corona pulse in the negative half-cycle increased as pressure was reduced. The repetition frequency of AC corona pulses increased with the rising of humidity. In the positive half-cycle, the variation trend of the number of AC corona pulse was not significant with the fall of air pressure. The repetition frequency of AC corona pulses in the negative half-cycle rose with the fall of air pressure.