Heat and Mass Transfer Coefficients of Liquid Desiccant Dehumidification/regeneration Processes with Non-Thermal Equilibrium(i) Model and Le-hD Evaluation Method

PENG Donggen,CAO Rongquan,ZHANG Xiaosong,YIN Yonggao
DOI: https://doi.org/10.3969/j.issn.0438-1157.2011.09.008
2011-01-01
Abstract:The liquid dehumidifiers are the key unit for liquid desiccant cooling system(LDCS)and the internal heat and mass transfer of dehumidifier have important influence on the performance of LDCS.Based on the adiabatic dehumidification model,a new model considering non-thermal equilibrium was put forward to evaluate heat and mass transfer coefficients.By simulation calculation,it is found that the outlet parameters of air and liquid from non-thermal equilibrium model agree well with the experimental values,so that the model is better to evaluate heat and mass transfer coefficients.When the heat capacity rate ratio C*≥1.0,the calculation results for the number of mass transfer units and Lewis factor from non-thermal equilibrium model are much better than those from the adiabatic model,while the two models give almost the same results when C*≤0.05.