Analysis of Electrical Tree Ageing in Silicone Rubber by Physicochemical Approach

Y X Zhou,Q Nie,Z,R Liu
DOI: https://doi.org/10.1088/1742-6596/183/1/012013
2009-01-01
Journal of Physics Conference Series
Abstract:In this paper, the characteristics of electrical tree ageing in silicone rubber (SIR) under AC voltage were studied. The electrical tree initiation rate is 20% after the application of 6 kV AC voltage for 1000 hours. Samples are separated into three kinds according to processes of electrical tree formation: virgin samples without voltage application, non-treed samples without electrical tree formation after 1000 hours and treed samples with electrical tree formation after 1000 hours. Certain physicochemical diagnostic tests were carried out to understand the degradation of material, ascribed to long-time voltage application, using differential scanning calorimetry (DSC) and thermogravimetric-differential thermal analysis (TG-DTA). Physicochemical analyses, especially the DSC results, show that no additional phases are formed in the processes of electrical tree ageing in SIR. Reduction of the melting point and crystallinity of SIR is observed in the sequence of virgin samples, non-treed samples and treed samples. The activation energy values were calculated from the TG-DTA data. Compared to virgin samples, obvious reduction of activation energy value is observed in non-treed samples. Degradation in SIR has already occurred before electrical tree formation and charge injection and extraction by high field electrode under AC voltage is regarded as the reason.