Simulation on Heat Transfer and Pressure Drop of R410A Two-phase Flow in Plate Heat Exchanger

Qiu Feng,Gu Bo,Zeng Weiping,Zhang Chunlu
DOI: https://doi.org/10.3969/j.issn.0253-4339.2010.01.039
2010-01-01
Abstract:The two-phase simulation models for a plate heat exchanger with R410A are established,and the error analysis and the comparison for the models are performed using the experimental data.Moreover,the factors to influence the performance of the heat exchanger are discussed.The average error of the modified model of condensation heat transfer is less than 5%.The accuracy of the modified model of evaporation heat transfer based on Yan and Lin increases by 10% compared with those in literature and its average error is 6.5%.In addition,the average error of the modified model of pressure drop including frictional pressure drop and port pressure drop on the basis of Yan and Lin model and Shah-Focke model is less than 2.5% and the maximum error is 8%.
What problem does this paper attempt to address?