Deadbeat Weighted Average Current Control with Corrective Feed-Forward Compensation for Microgrid Converters with Nonstandard LCL Filter
Jinwei He,Yun Wei Li,Dehong Xu,Xiaodong Liang,Beihua Liang,Chengshan Wang
DOI: https://doi.org/10.1109/tpel.2016.2580005
IF: 5.967
2016-01-01
IEEE Transactions on Power Electronics
Abstract:Microgrid converters are required to have the capability of both grid-tied mode and islanding mode operation. For this dual-mode operation, large shunt capacitors are often used in the interfacing converter output LCL filter, as it can help to stabilize supply voltage and to reduce switching ripple pollutions to sensitive loads during autonomous islanding operation. At the same time, this modification causes a few challenges, including the low-frequency harmonic distortions, the steady-state tracking errors and the slow dynamic response, to the line current regulation during grid-tied operation. To overcome these drawbacks, a modified weighted average current controller is developed. First, to realize a fast line current response, a deadbeat control of weighted average current is developed based on a reduced-order virtual filter plant. Second, a grid voltage feed-forward term is added to the weighted average current reference to mitigate the steady-state line current tracking errors. Note that this compensation term is directly added to the current reference, thus, it is very well decoupled from the closed-loop current regulator. In addition, it can be seen that the low-order line current harmonics caused by grid voltage distortion is inherently compensated by this proposed corrective feed-forward control.