Research of Smear-type Surface Evaporative Cooler Performance Test

Tang Xinshao,Xiao Yimin
DOI: https://doi.org/10.3969/j.issn.1671-6612.2011.02.001
2011-01-01
Abstract:This paper proposes a form of evaporative cooling,which is smearing water on outside surface of coil heat exchanger.Through experiments we researched the following factors effect on the heat transfer performance test,discharge of smearing water and rotation speed,diameter of the coil heat exchanger,length of the coil heat exchanger,heat exchanger treated water flow and moisture content of air.Experimental results show that the moisture content of air for every 1% increase,heat transfer per unit area decreased about 2%.Were carried out five experiments dealing with water flow compared with three different sizes of heat exchangers,optimization is given for the heat production and work flow specifications.