Single-Ended Transient-based Protection for EHV Transmission Lines Basic Theory

DUAN Jian-dong,ZHANG Bao-hui,REN Jing-feng,LUO Si-bei,HA Heng-xu,ZHOU Yi
DOI: https://doi.org/10.3321/j.issn:0258-8013.2007.01.007
2007-01-01
Abstract:Study on characteristic of transmission system in detail is important to effectively use fault transient components, which contain abundant fault information. The paper applies frequency domain model of transmission system to analyze the frequency characteristics of transmission line, busbar and line trap. Then presents that the surge impedance of busbar capacitance and line trap is different from transmission line, and based on which proposes the concept ‘line boundary’. Through discussing further the reflective and refractive coefficients of line boundary, the features of line boundary are as follows: the attenuation of high frequency band (especially in band of line trap) of transient components generated by fault through line boundary is obvious, whereas the low frequency band (1~10kHz) components are hardly influenced. Moreover, the transient components below 100kHz should be adopted in purpose of outstanding the line boundary and weakening the transmission influence of transmission line. The paper is significant for other traveling-wave or transient-based protection researches.
What problem does this paper attempt to address?