A New Hysteresis Control Method for Active Power Filter

何易桓,张代润,张竹,王超
DOI: https://doi.org/10.3969/j.issn.1000-100x.2009.10.011
2009-01-01
Abstract:In view of the time delay phenomenon of three-phase four-wire system active power filter when exterior A/D is used,which makes control inaccurate,a new hysteresis current control strategy is proposed.A new band width is established,which is used to judge whether there is a dead area.When the compensation current is in bandwidth range and zero crossing,the dead area exists,otherwise it exits.Then the general hysteresis control method is used to produce PWM driving signal and to achieve the effect of restraining switch time delay and the dead area time delay.The simulative and the test results indicate that the superiority of this algorithm is obvious and the current compensation effect is good.
What problem does this paper attempt to address?