Experimental Study on a Closed Wet Anti-White Mist Spray Cooling Tower

金深洋,金惠珍,夏再忠,陈传涓,陆紫生
DOI: https://doi.org/10.3969/j.issn.1009-2455.2010.04.020
2010-01-01
Abstract:In order to avoid the formation of white mist in the outlet airflow coming from cooling towers,a closed wet spray cooling tower was designed and manufactured.In the said cooling tower,cooling water is separa-ted and cooled in wet heat exchanger and dry heat exchanger respectively.In the wet heat exchanger,which adopts copper fin tubes as heat transfer tubes,cooling water is chilled inside the heat transfer tubes while heat and mass transfer between spray water and airflow is observed outside the copper tubes.The airflow with low tem-perature and high humidity flows across the dry heat transfer,and then,heated by the cooling water in copper-aluminum combined fin tubes,which causes a high outlet temperature of the airflow.As a result,when the outlet airflow mixes with ambient air,the mixed airflow is unsaturated,which avoid the formation of white mist.