Performance Characteristics of Heat-Regenerative NH3-H2O Absorption Refrigeration System Without Solution Pump and Distillation Equipment

WANG Jing,WU Yu-yuan,WU Tie-hui,HE Shu-qing
DOI: https://doi.org/10.3321/j.issn:1006-2467.2009.02.034
2009-01-01
Abstract:A novel heat-regenerative NH_3-H_2O absorption refrigeration system without solution pump and distillation equipment was proposed,in order to make full use of residual waste heat of weak solution.Some improvements were made for existing system,by adding a generator and three solution heat exchangers into each generator.The results indicate that the coefficient of performance(COP) could be up to(0.295),with the new defined parameter—solution circulation coefficient(λ) is set to 1,which is 82.1% more than that of the original cycle.When λ increases,both the warm-up heat load and the required fore-cooling load could be reduced significantly,which leads to enhance COP evidently and improve the refrigeration continuity of the system.The higher the solution recycle ratio of λ,the more advantages of the heat-regenerative system.
What problem does this paper attempt to address?