Controllable Load Used to Improve Grid Voltage Stability

Xuemei HE,Rongxiang ZHAO,Huan YANG
DOI: https://doi.org/10.3969/j.issn.1005-2895.2013.04.014
2013-01-01
Abstract:Voltage stability issue is widely concerned due to power grid accident caused by voltage collapse in recent years.Instead of solving this problem from the generation side,controllable loads were applied to improve grid voltage stability.Variable-speed air-conditioner equipped with converter accounts for a large part of the total load.Accordingly,variable-speed air-conditioners were used as controllable load to alleviate negative influences of induction motors on power system during voltage disturbance.Firstly,the models of variable-speed air-conditioner were given and analyzed.Then,rather than the centralized control strategy,decentralized control strategy based on droop characteristics of variable-speed air-conditioners were designed to improve voltage stability once grid faults happened.The strategy can automatically adjust the power consumption of variable-speed air-conditioner according the real-time detection of grid voltage without the use of communication devices.To verify the effectiveness of controllability and control strategy of variable-speed air-conditioner,Matlab/Simulink was applied for simulation.