Influence of Inlet Air Flow Direction to the Performance of the Quasi-Counter Flow Total Heat Exchanger

Yan-wen LIU,Zhen-hai LI
DOI: https://doi.org/10.3969/j.issn.1673-7237.2012.01.003
2012-01-01
Abstract:An analogy was drawn between fluid-solid(membrane) coupled moisture transfer and fluid-solid coupled heat transfer by reasonable assumptions.A coupled moisture and heat transfer mathematic model was established between air and membrane.Then the model was implemented in the present CFD code Fluent,and verified by experimental works.Keeping the air flow rate as a constant,the performance parameters of the exchanger were calculated under various inlet air flow directions.It indicates that the best performance is obtained when the direction is between 75 degree and 90 degree.The reason was analyzed by defining the distribution coefficient of air flow.
What problem does this paper attempt to address?