The Analysis of Maximum Capacity of DG Connected to Guizhou High Voltage Distribution Network

李庆生,沈欣炜,郑竞宏,李金霞,朱守真
DOI: https://doi.org/10.13941/j.cnki.21-1469/tk.2013.08.024
2013-01-01
Abstract:this paper presents a method that analysis the maximum capacity of Distributed Generation connected to a high voltage distribution network。 This method is applied in power grid planning in Guizhou province to analyze the maximum capacity of DG.According to a few anlysis cases in Guizhou,the article studies the law that how DG affects the node voltage when connected to a high voltage distribution network,and discusses the relationship between the two factors-node voltage limitation and transmission capacity constraint.The results show that generally DG rises the node voltage,but when DG capacity is large,the node voltage can be falling instead of rising due to the active,reactive power loss in the transmission line,which prevets the node voltage from rising over limitation.And the restrictive factors of DG grid-connected capacity based on several analysis results in Guizhou are discussed at the same time.
What problem does this paper attempt to address?