Method for Unbalanced Voltage Sags Detection Based on Dq Transform

LIU Yun-chan,HUANG Chun,OU Li-quan,ZHAO Wei-ming
DOI: https://doi.org/10.3969/j.issn.1003-8930.2007.03.013
2007-01-01
Abstract:The voltage sag detection based on dq transform is usually used in dynamic voltage restorer(DVR),but it is only applicable to symmetrical voltage sags.A method for unbalanced voltage sags detection is presented,which can identify unbalanced voltage sags characteristics,such as magnitude,duration and phase-angle jump.The positive,negative and zero sequence can be obtained by using dq transform and morphological filter,and then voltage sags characteristics can be calculated.Simulation results prove that the proposed method is correct and it has better dynamic performance.The real time requirement of DVR can be satisfied with the proposed method.