Effect of automatic recirculation flow control on the transient response for Lungmen ABWR plant
Yih-Chyun Tzang,Ray-Feng Chiang,Yuh-Ming Ferng,Bau-Shei Pei
DOI: https://doi.org/10.1016/j.nucengdes.2009.09.005
IF: 1.7
2009-01-01
Nuclear Engineering and Design
Abstract:In this study the automatic mode of the recirculation flow control system (RFCS) for the Lungmen ABWR plant has been modeled and incorporated into the basic RETRAN-02 system model. The integrated system model is then used to perform the analyses for the two transients in which the automatic RFCS is involved. The two transients selected are: (1) one reactor internal pump (RIP) trip, and (2) loss of feedwater heating. In general, the integrated system model can predict well the response of key system parameters, including neutron flux, steam dome pressure, heat flux, RIP flow, core inlet flow, feedwater flow, steam flow, and reactor water level. The transients are also analyzed for manual RFCS case, between the automatic RFCS and the manual RFCS cases, comparisons of the transient response for the key system parameter show that the difference of transient response can be clearly identified. Also, the results show that the ΔCPR (delta critical power ratio) for the transients analyzed may not be less limiting for the automatic RFCS case under certain combination of control system settings.