EXCITATION CONTROL FOR GRID-CONNECTED DOUBLY FED GENERATOR

Zou Xudong,Zhao Yang,Kang Yong,Chen Jian
DOI: https://doi.org/10.3321/j.issn:0254-0096.2007.09.013
2007-01-01
Abstract:According to the mathematical model of doubly-fed induction generator (DFIG),the detailed analysis of how to deal with coupled system variables by space vector control methods was presented.Based on stator-flux orientation control strategy,two excitation control models aiming at different control modes of grid-connected doubly-fed induction generator system were formed.An analysis of the difference between the two control modes is also showed.Experimental results and theoretical analysis all prove that this method of dealing with system coupled variables with back electromotive force feed- forward compensation could effectively suppress the grid voltage fluctuation and enhance the dynamic response perfor- mance of the whole system.The power control mode can achieve the active and reactive power decoupled control,while speed control mode can do the active power and the speed decoupled control,but the separately synchronous control among the three is unable to attain.
What problem does this paper attempt to address?