Resonant-based sliding mode control of doubly-fed induction generator connected to unideal grid

QUAN Yu,NIAN Heng
DOI: https://doi.org/10.3785/j.issn.1008-973X.2014.04.003
2014-01-01
Abstract:The resonant-based sliding mode control was proposed in order to enhance the operation performance of doubly-fed induction generator(DFIG)connected to grid with unbalanced and harmonic voltage.In order to ensure the stable stator output active/reactive power,the power tracking errors under unbalanced and harmonic grid voltage were avoided by applying the resonant controller tuned at the 6th fundamental frequency in the switching surface of the sliding mode control.Then the stability and convergence capability of the proposed control strategy were analyzed.The experiments of the DFIG system were conducted under the unbalance and harmonics distorted grid.The stable stator output active/ reactive power was achieved based on the proposed strategy,which validates that the resonant-based sliding mode control strategy can achieve the more stable control performance and dynamic response capability compared with the integral sliding mode control.
What problem does this paper attempt to address?