Abstract:AbstractThis paper presents a new method of simulating transient responses of multimachine power systems following a large disturbance. The conventional model used in the simulation is composed mainly of synchronous machine models in which the armature transients are neglected, and steady‐state transmission system equations. This is because it is very difficult to treat the transmission system and the armature circuits of synchronous machines as differential equations. Naturally, the model cannot evaluate the effects of these neglected transients. The new method proposed herein uses the new synchronous machine model and the steady‐state transmission system model. The former is obtained by modifying slightly the conventional armature‐transient neglected model. Thus the resultant simulation model has almost the same structure as the conventional one. However, it can evaluate approximately the effects of armature transients on the dynamical behavior of the synchronous machines. For example, it can evaluate easily the angular backswing following a three‐phase short‐circuit fault. In addition, the new method can also estimate the maximum values of developed torque, induced voltage and armature current of synchronous machines at the moment when the disturbance occurred and when it was cleared.