Experimental investigation of a micro-combined cooling, heating and power system driven by a gas engine

X.Q. Kong,R.Z. Wang,J.Y. Wu,X.H. Huang,Y. Huangfu,D.W. Wu,Y.X. Xu
DOI: https://doi.org/10.1016/j.ijrefrig.2005.04.006
IF: 4.14
2005-01-01
International Journal of Refrigeration
Abstract:An experimental investigation of the performance of a micro-combined cooling, heating and power (CCHP) system is described. The natural gas and LPG-fired micro-CCHP system uses a small-scale generator set driven by a gas engine and a new small-scale adsorption chiller, which has a rated electricity power of 12kW, a rated cooling of 9kW and a rated heating capacity of 28kW. Silica gel–water is used as working pair in the adsorption cooling system. The refrigeration COP of the adsorption chiller is over 0.3 for 13°C evaporation temperature. The test facility designed and built is described, which supplies better test-rig platform for cooling, heating and power cogeneration. Experimental methodology of this system is presented and the results are discussed. An energetic analysis of micro-CCHP system is performed as well. The overall thermal and electrical efficiency is over 70%.
What problem does this paper attempt to address?