Level Noise Simulation Using Time Series Analysis

WANG Fang-yuan,CAO Xiao-lin,LIU Yong-wen,SU Ming
DOI: https://doi.org/10.3969/j.issn.1006-9348.2005.11.017
2005-01-01
Abstract:In combined cycle power plant,drum level control system is often affected by level noise.If this affection has not been taken into account in simulation environment,the control system developed by it may fail in the field.Most of the existing heat recovery boiler models can't accurately simulate the noise content in level signal.To solve such problem,by using time series analysis,a noise model is provided in this paper.According to the field data,the model rebuilds level noise signal in time domain,and the signal's PSD(power spectrum density) is close to the PSD of the field data in frequency domain.The model can be used as a reliable base to develop control strategy for drum level control system.
What problem does this paper attempt to address?