INVESTIGATION ON FALLING FILM FLOW AND HEAT TRANSFER CHARACTERISTICS INSIDE CORRUGATED TUBE

Sun Hejing,Zhu Dongsheng,Wu Zhijiang,Tang Xinyi
DOI: https://doi.org/10.3969/j.issn.1005-2399.2009.10.006
2009-01-01
Abstract:Falling film flow in vertical corrugated tube and circular tube was simulated by CFD software respectively,and a vertical evaporative condenser test platform was adopted to measure the temperature and flow rate under various spray densities.The heat and mass transfer coefficient of each phase interface inside corrugated tube was calculated based on the experimental data,and it was compared with that of inside circular tube under the same conditions.Simulation results indicate that at the same spray density,the water-film distribution in vertical corrugated tube is better than that of in circular tube.Experimental results show that with the increase of spray density in a certain range,the heat transfer coefficient of water-film,equivalent heat transfer coefficient of air-water and total heat and mass transfer coefficient increase.In addition,the heat transfer performance of corrugated tube is significantly better than that of circular tube.
What problem does this paper attempt to address?