Mathematical Simulation of Pool Fire in Fire Bund of Large Oil Tank Zone Based on FDS

Li Qinggong,Song Wenhua,Chen Zhen,Lü Lingyue,Feng Lili
DOI: https://doi.org/10.3969/j.issn.0465-7942.2012.01.014
2012-01-01
Abstract:The pool fire in fire bund of one large oil tank area,whose total capacity was 106 m3,was simulated by the fire simulation software FDS.The object of simulation was the most unfavorable fire bund for fire rescue.The way of setting fixed heat release rate of FDS was adopted in combustion model,and the heat release rate was set for 1 500 kJ/m2.The simulation results indicated that the height of flame was 55 m and the highest temperature of the surface of adjacent tank was 160 ℃.With the development of fire,the fire behaviour became stable.When the influence of atmospheric flow was considered,the thermal radiation strength value of pool fire in tank bund was about 25 kW/m2 for adjacent tank.
What problem does this paper attempt to address?