Topology and Experimental Study on a Novel Magnetic-Controlled Switcher Type Fault Current Limiter

PAN Yan-xia,LING Zhi-bin,CAI Xu,JIANG Jian-guo
2008-01-01
Abstract:Based on the topology of saturated iron core high temperature superconducting fault current limiter (FCL), a new magnetic-controlled switcher type FCL suitable to medium and high voltage power network is proposed. A current-limiting inductance is series in bias circuit, the current-limiting inductance can be automatically inserted or disconnected according to variation of AC current before and after fault, so fault current limiting is realized. An experimental prototype of 220V/50A limiter is developed. The experimental results of this prototype of FCL show that the magnetic-controlled switcher type FCL possesses following advantages: the voltage drop across the FCL is very low under its normal operation, so there is almost no affect on transmission line; when transmission line fault occurs the current-limiting inductance can be automatically inserted into faulty line; this type of FCL basically does not generate harmonics, its control is flexible, simple and reliable as well as the short-circuit current of transmission line can be limited swiftly and effectively.
What problem does this paper attempt to address?