ANALYSIS OF THERMAL ECONOMIC BEHAVIOR FOR ADOPTING COOL- ELETRICITY CO- GENERATION TO 300 MW EXTRACTION CONDENSING UNIT

FAN Jiang,WANG Jin,WANG Yu
DOI: https://doi.org/10.3969/j.issn.1002-3364.2007.03.002
2007-01-01
Abstract:Based on characteristic parameters of the hot water two-section type lithium bromide absorbing refrigeration machine and the parameters of the central heating system in Taiyuan City proper, the thermal economic behavior of adopting cool-electricity cogeneration to 300 MW extraction condensing unit has been calculated and analysed. The results of calculation show that the energy-saving effect to be remarkabe if the thermal coefficient of lithium bromide absorbing refrigeration machine isn’t less than 0.825, the coal consumption rate of power supply in the gride isn’t less than 0.388 kg/kWh, the line loss rate isn’t lower than 6.98%, and the refrigeration coefficient of electric motor driven refrigeration machine isn’t higher than 3.5.
What problem does this paper attempt to address?