The Air Velocity Research of Ammonia Refrigeration Refrigeratory

王东礼,王文生,董成虎,李华江
DOI: https://doi.org/10.3969/j.issn.1009-6221.2010.01.008
2010-01-01
Abstract:The experiments were made in cang mountain of shandong cold-chain logistics base to describe cold air velocity in refrigeratory. The result showed that, air velocity of upper shelf,shelf path and whole center path in empty refrigeratory are differ than full,but they are the same of lower shelf and shelf path. Air velocity of most area in the full refrigeratory can’t reach the standard condition and suggest that optimize air path,use double velocity or frequency conversion fanner,control the air velocity in pre-cooling between 0.80 to 1.00 m/s and in storage period between 0.30 to 0.50 m/s.