Performance optimization analysis for thermal-driven concentration variance liquid dehumidification systems

Xiong Zhenqin,Dai Yanjun,Wang Ruzhu
DOI: https://doi.org/10.3969/j.issn.1002-8501.2008.11.018
2008-01-01
Abstract:Proposes a method of enlarging the concentration variance of dehumidification solution and improving the operation performance of the system.This system can better adapt with unstable energy source such as solar heat.Analyses the performance of the system with a theoretical model validated by preliminary experiment,the result shows that the COP of the system with calcium chloride as refrigerant reaches 0.89 at the regeneration temperature of 73.2 ℃,improved by 89.4 percent than that of a single circulation solution dehumidification system and the dehumidifying capacity per kilogram solution of 45 percent calcium chloride increases from 3.92g to 122.83g.
What problem does this paper attempt to address?