Winter Indoor Thermal Comfort and Its Influence on Energy Consumption of Air-conditioning System of Office Buildings in Nanning

Li-xing ZHENG,Wei LU,Hong-jie CHEN
DOI: https://doi.org/10.3969/j.issn.1002-8528.2011.10.009
2011-01-01
Building Science
Abstract:In this paper,according to the questionnaire and field test,the winter indoor thermal comfort of office buildings in Nanning was analyzed with the index of standard effective temperature(SET),and the results were compared with those of other domestic regions.The results indicated that 80% people felt comfortable when the temperature ranged from 14.4 ℃ to 23.7 ℃ in SET,and the neutral temperature of thermal sensation was 19 ℃ in SET.The local residents were less sensitive to thermal environment than those in other domestic regions.Furthermore,in the residents' acceptable range of indoor thermal comfort,air-conditioning system energy consumption increased with the rising of SET.In addition,if the neutral temperature was taken as the indoor design parameter and was compared with the specified value in national and local standards,the air-conditioning system energy consumption in Nanning would decrease by 6.4%.
What problem does this paper attempt to address?