Experimental Study on the Control of Boilover Fire of Oil Tank

Jia-lei TAN,Tong WANG,Ruo-wen ZONG,Guang-xuan LIAO,Yu ZHANG
DOI: https://doi.org/10.3969/j.issn.1003-3033.2009.01.008
2009-01-01
Abstract:Firstly, the three basic prerequisites for the formation of boilover were analyzed, and the definition of boilover triangle was presented. Then, the idea of preventing boilover fire from forming through destroying one of the three prerequisites was put forth. To testify this idea, a small-scale experiment platform for boilover fire prevention was built, and the zeolite and the serpentinepipe cooling system were respectively applied to the experiment of boilover prevention. Through a contrast analysis on the temperature of oil layer, oil-water interface, water layer and radiation before and after, it is founded that the zeolite and serpentinepipe cooling system can effective restrain the formation and prevent the harmfulness of boilover. This study can provide theoretical foundation for the prevention of boilover fire.