Study of Thermal Environment in Office and Market Buildings of Xi'an in Winter

YUAN tao,LI Jian-dong,WANG Zhi-chao,LIU Yun,YANG Ying-xia
DOI: https://doi.org/10.3969/j.issn.2095-3429.2010.05.018
2010-01-01
Abstract:Five office buildings and three market buildings were studied in Xi’an in January 2010.Temperature,humidity and other thermal parameters were tested,and questionnaires were collected.Results indicated that city heating steam and gas-fired boilers were the major heat resource forms.The average temperature in office and marketplace were 19.9℃ and 21.1℃ respectively,which both satisfied the demand for thermal comfort air-conditioning system.However,the average temperature of marketplace was a little higher,which could’t meet the energy-saving demand.Relative humidity of air in both type buildings was lower than 30%,which showed that the inner air was too dull.Distribution of thermal sensation,thermal comfort and thermal satisfaction were got based on questionnaires.More than 83% of people in office and marketplace feel satisfied or just-satisfied.Neutral temperatures in office and marketplace were 18.8℃ and 18.7℃ respectively,and corresponding temperature zone of thermal comfort which accepted by more than 80% people were also obtained.