Simulation and analysis of air distribution inside heat passage of glass curtain walls

Li Rongmin,Gu Jianming
DOI: https://doi.org/10.3969/j.issn.1002-8501.2007.01.005
2007-01-01
Abstract:With finite element analysis software ANSYS, simulates the flow field and the temperature field inside the heat passage of glass curtain wall applying natural ventilation and mechanical ventilation for the ward building in Shanghai First People’s Hospital, and finds that natural ventilation effect can not be realized and that applying mechanical ventilation can achieve good ventilation effect and save energy. For improving natural ventilation effect, proposes setting an inner glass at a distance of about 0.8 m from the external wall, and simulation results show that air outlet velocity can reach about 2.3 m/s and heat can be effectively removed from curtain wall. Simulates the velocity and temperature fields inside glass curtain walls with various widths of curtain wall and heights of air inlet and outlet under the condition of the same boundary and curtain wall height as the above model, considers the curtain wall width of 1.4 m and the air inlet and outlet height of about 0.35 m optimal design dimensions.