Energy Efficiency Analysis on Quality Regulation of District Cooling System in Guangzhou University Town

Jun-wei YAN,Fei-long LIU,Dong-sheng ZHU,Xuan ZHOU,Jing LI
DOI: https://doi.org/10.3969/j.issn.1002-8528.2007.12.007
2007-01-01
Building Science
Abstract:In this paper,according to the theory that cooling load of air-conditioning system would change with the variation of outdoor temperature,the strategy of quality regulation that could provide required cooling capacity was introduced.Based on the weather condition and the actual cooling load characteristics in Guangzhou university town,the temperature curves of supply and return chilled water under different outdoor temperatures were given out,also the effects of quality regulation on second grade cooling capacity exchange station and fan coils were discussed.After this strategy was used in South China University of Technology,the temperature difference of supply and return chilled water increased to 12 ℃,and the load rate of chilled water flow decreased to 50%,therefore,the district cooling system with large temperature difference and small flow rate was achieved.