Experimental Study of Circulating Cooling Water Scale Inhibition by Low Voltage Electrostatic

Quan Zhenhua,Wang Chunming,Li Bing,Chen Yongchang,Ma Chongfang
DOI: https://doi.org/10.3969/j.issn.1009-0177.2007.06.008
2007-01-01
Abstract:The scale inhibition performance of low voltage electrostatic in the circulating cooling water system was investigated and its mechanism was identified.A series of fouling tests were carried out by dynamically monitoring fouling resistance and the water qualities were analyzed.It was shown that the fouling was effectively restrained to form on the surface of the heat exchanger if the circulating cooling water was treated with low voltage static electricity.When the power was about 2.2W,the scale inhibition reached 100%.The hardness,alkalinity,electrical conductivity,and pH of the solution were decreased with the treatment.The low voltage electrostatic water treatment is an inactive scale inhibition technology,which is different from the other physical water treatment technologies.The mechanism of scale inhibition is that the micro electrolysis reactions occur nearby the electrode due to the low current existing in the water,so most fouling forms in the solution nearby the cathode or on the inner surface of treatment unit,but not depositing on the surface of the heat exchanger.In addition,the electrostatic field contributes to inhibition enhancement.
What problem does this paper attempt to address?