Experiment on Free Cooling Unit for a Telecommunication Base Station

陈杰,马国远,周峰
DOI: https://doi.org/10.3969/j.issn.2095-4468.2012.03.107
2012-01-01
Abstract:The power consumption of air conditioning for a telecommunication base station(TBS) in China occupies almost 40%of the total power consumption.In order to reduce the power consumption,a free cooling unit with working fluid of glycol-water unit was designed for the base station to share the cooling load with the air conditioning,and the prototype also have been tested.The results indicate that the free cooling unit works well with a good heat dissipation performance under the testing conditions.The temperature efficiency of the unit can reach 45%and the heat transfer coefficient reaches 60 W/(m~2·℃)。