Effect of Ventilation and Filtration on Submicrometer Particles in an Indoor Environment.

M Jamriska,L Morawska,BA Clark
DOI: https://doi.org/10.1034/j.1600-0668.2000.010001019.x
IF: 6.5539
2000-01-01
Indoor Air
Abstract:The effect of filtration and ventilation on reduction of submicrometer particle concentration indoors was investigated in an office building. The air-handling system consisting of dry media filters and an air-conditioning unit, reduced particle concentration levels by 34%. The characteristics of indoor airborne particles were dominated by, and followed the pattern of, outdoor air, with vehicle combustion aerosols as the main pollutant. The ratio indoor/outdoor particle concentration varied between 14 and 26% for different sub-zones. The presence of significant source of particles indoors was not observed. A simple mathematical model predicting evolution of particles indoors is presented. The model, based on a particle number balance equation, was validated with experimental data and showed very good agreement between predicted and measured parameters.