The Harmonic Analyses of the Large Industrial Scale Chemical Electrolyzers' Rectification Equipment

Ding Guoliang
DOI: https://doi.org/10.3969/j.issn.1004-017X.2007.04.011
2007-01-01
Abstract:This paper narrates the reason of the electrolysis-rectification equipment's current aberration and introduces the utility grid harmonic standards and the method of harmonic calculation.It illuminates that when the equivalent 12 impulses rectification produced by a single rectify-transfomer in a large electrolysis-rectification equipment,the 11&13 harmonic current virtual value is beyond the GB standards,but the 23&25 harmonic current virtual value is not beyond the GB standards with an example of a large industrial scale chemical electrolyzers'rectification equipment harmonic calculation.So,in order to meet the GB standards,we need 24 impulses rectification in theory.