Simulation Study on Coordinated Control System of Subcritical 600 MW Unit

ZHANG Hefei,YU Yuefeng
DOI: https://doi.org/10.3969/j.issn.1002-3364.2013.04.031
2013-01-01
Abstract:Combined with the operation parameters of Wu Jing Second Power Plant,the mathematic model for coordinated control system in a subcritical 600 MW unit was established,on the basis of the coordinated control model.By Simulink software,simulation on this model was conducted and the results were compared with the unit operation data.With a constant opening degree of regulating valve,when the coal feed quantity was changed,the maximum error between the simulated value and actual value of the main steam pressure was below 0.3 MPa,and that of the turbine power was less than 3 MW.When the coal feed quantity was kept constant and the opening degree of regulating valve varied,the maximum error between the simulated value and actual value of the main steam pressure was within 0.2 MPa,and that of the turbine power was below 4.5 MW.The small dynamic error between the model and the unit operation demonstrated the feasibility of the above mathematic model for coordinated control system.Based on this model,the unit coordinated control system was improved,by direct energy balance(DEB) method.The simulation results showed that,the improved unit coordinated control system had high response speed and strong anti-interference,and can control the fluctuation of main steam pressure well.
What problem does this paper attempt to address?