Research on Directional Protection for Ship Power Grid

HUANG Bin,TAI Nengling,WANG Peng,NI Mingjie,WEI Wei,ZHANG Shurong
2013-01-01
Abstract:Electric motor will run into a generator when ship power grid has short circuit faults at any point and will feedback short circuit current to the fault point.Based on the basic principle of directional protection,this paper analyzes the short circuit condition of ship and the feedback short circuit current of electric motor.The results show that during the transient process the short circuit feedback current provided by large capacity motor can reach 10 times rated current,and feedback current increases with the growing capacity of electric motor.The over-current relay protection at the branch export may be unwanted operation.On the basis of this conclusion,in order to distinguish the fault direction and guarantee the ship grid's safe operation,we propose some recommendations for power directional relay installation in motor branch.
What problem does this paper attempt to address?