Ice-shedding Characteristic of 1000 kV AC Double Circuit Transmission Line on the Same Tower

Wei Hu,Yong Chen.,Wei Cai,Xiaobo Meng,Liming Wang,Guanjun Fu,PuXuan Zhu
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.01.003
2010-01-01
Abstract:The rules of ice-shedding characteristics were acquired by simulation tests,and various span configurations as well as ice-shedding mode were taken into consideration.Furthermore,numerical computation was done according to the test conditions.Good agreement between the computational and test results was obtained which proves the validity of both the test and numerical methods.Then a 3DOF(degree of freedom) dynamic model of multi-span line suitable for analyzing UHV ice-shedding was presented.The influential factors including multi-span configuration,span length,number of spans per line section,and mechanical parameters of conductor are studied.The ice-shedding height of UHV was analyzed when the icing thickness was 15 mm.Results show that interphase conductors of UHV double circuit transmission line needn't have horizontal displacement at the condition of 15 mm ice thickness and below.When the ice-shedding from the conductor happens,the lines can also work safely.