Producing Mechanism and Ventilation Control of Radon in Underground Space

Liu Peiyuan,Yao Yang,Wang Qingqin,Chen Pengfei
DOI: https://doi.org/10.3969/j.issn.1003-0344.2006.03.017
2006-01-01
Abstract:In this paper,the radon emanation model equations of soil and material are established.Considering each affected factor,the exterior emanation rate formula for the soil and building material were deduced,on the basis of which,the relation of indoor radon concentration and air change rate was deduced also.One typical underground space was calculated according to the formula obtained,and it was found that the main source of radon in underground space comes from the radon overflow in the soil which accounts for 70%~90% of the total radon emanation volume,and it was also found that indoor radon concentration is very sensitive to ventilation at the higher radon concentration.When increasing the air change rate in the underground space,the radon concentration in the air will fall fast.According to standards for the fresh air volume of underground space,the indoor radon concentration can be controlled under 400 Bq/m3easily.But when trying to control the indoor radon concentration under 200 Bq/m3,the fresh air volume per person must be above 25.2 m3/h.Considering that the fresh air can not be utilized completely,the outdoor air volume should be higher than 31.5 m3/h.
What problem does this paper attempt to address?