Analysis of Dynamic Stability Characteristics of 750 Kv Northwest China Power Grid and Research on Its Control Strategy

LI Yang-nan,LIU Wen-ying,PAN Wei,CHENG Lin,SHI Ke-qin,FAN Yue
DOI: https://doi.org/10.3321/j.issn:1000-3673.2007.12.012
2007-01-01
Abstract:The main 750kV power network of Northwest China Power Grid will be built up preliminarily in the year of 2008, the dynamic stability of Northwest China Power Grid under the operating mode of transmitting power from West China to East China at that time is analyzed and compared with present situation of Northwest China Power Grid. Simulation results show that after the building up of 750kV main power network the dynamic stability of Northwest China Power Grid will be improved. Due to the relative weakness of the 750kV main power network, the insufficient damping caused by the outage of 750kV tie-line, which connects Shaanxi power network with Gansu power network, may lead to low frequency oscillation, so that it will be necessary to configure PSS to ensure stable and secure operation of Northwest China Power Grid. Based on the results from time-domain simulation, small signal stability analysis, Prony analysis and residual method, the configuration of PSS in the 750kV power network of Northwest China Power Grid and corresponding optimal parameter setting scheme are proposed. Calculation results show that the proposed scheme is valid.
What problem does this paper attempt to address?