Parameters Optimization of VDCOL Connected to AC Power Systems with Different Strength

Ming XU,Zhi-gang WU,Dong-dong SU,Bao-rong ZHOU
DOI: https://doi.org/10.3969/j.issn.1673-9140.2013.02.011
2013-01-01
Abstract:The rule about how the control parameter of VDCOL varies with the strength of AC power system is studied in this paper.The influence of electrical connection strength and the access mode of HVDC on short-circuit capacity is analyzed in detail.The rule is explained from the power system stability point of view.Study results show that the electrical distance of the receiving power system and the input impedance of the HVDC system affect the short-circuit capacity more dramatically.The stability type changes from angle stability to voltage stability for the same fault near the converter station with the decrease of the system short-circuit ratio(SCR) as well as the effective short-circuit ratio(ESCR).The V-I curve of VDCOL shifts to the right during the decreasing.Simulation results for different operating conditions of the system show the general property of the rule.It is useful for VDCOL parameter setting when a certain HVDC system is connected to different AC power systems.
What problem does this paper attempt to address?