Dynamic process of high-current vacuum arc with consideration of magnetic field delay: numerical simulation and comparisons with the experiments

Dingge Yang,Lijun Wang,Shenli Jia,Xintao Huo,Ling Zhang,Ke Liu,Zongqian Shi
DOI: https://doi.org/10.1088/0022-3727/42/6/065204
2009-01-01
Abstract:Based on a two-dimensional magnetohydrodynamic model, the dynamic process in a high-current vacuum arc (as in a high-power circuit breaker) was simulated and analysed. A half-wave of sinusoidal current was represented as a series of discrete steps, rather than as a continuous wave. The simulation was done at each step, i.e. at each of the discrete current values. In the simulation, the phase delay by which the axial magnetic field lags the current was taken into account. The curves which represent the variation of arc parameters (such as electron temperature) look sinusoidal, but the parameter values at a discrete moment in the second 1/4 cycle are smaller than those at the corresponding moment in the first 1/4 cycle (although the currents are equal at these two moments). This is perhaps mainly due to the magnetic field delay. In order to verify the correctness of the simulation, the simulation results were compared in part with the experimental results. It was seen from the experimental results that the arc column was darker but more uniform in the second 1/4 cycle than in the first 1/4 cycle, in agreement with the simulation results.
What problem does this paper attempt to address?