Statistics Characteristics of Leakage Current on Artificial Contamination Test of Insulator

HE Bo,LIN Hui
DOI: https://doi.org/10.3969/j.issn.1003-6520.2006.08.002
2006-01-01
Abstract:In order to build effective online monitoring method for contaminated insulators and prevent flashover from happening, the right measuring signal and method must be predetermined. In this paper, statistics characteristics of leakage current were studied basing on a large number of data obtained from artificial contamination test, the factors influencing leakage current significantly were found and a regression equation was established. The results indicate that leakage current has close relationship with RH (relative humidity) and RH persisting time length during test, these two factors affect the leakage current value obviously, while the relationship between leakage current and temperature is poor. Partial correlation result shows that temperature affects the leakage current Mainly through influencing RH indirectly. All these have practical significant for developing right online monitoring technology for insulator state recognition and establishing the flashover forecast system basing on LC analysis.
What problem does this paper attempt to address?