Abstract:In this paper,we focus on the solution for doubly-fed induction generator(DFIG) based wind farm to achieve the control objective in the second period of asymmetrical grid faults ride-through,which is to support the network voltage by means of additional reactive current required by the grid codes while keeping connecting to the power grid with safe operation.However,the proposed control targets cannot be always satisfied due to the converter capacity constraint of the DFIG-based wind energy conversion system(WECS).Therefore,the controllability of DFIG are analyzed by optimal method while its controllable regions presented by unbalanced degree of grid voltage is given,which points out that static synchronous compensator(STATCOM) with the function of reducing unbalanced degree of fault voltage is essential to the DFIG-based wind farm under severe fault situations.At the last,a voltage compensation control scheme needing minimum capacity of the STATCOM is proposed and respective capacity matching method is also given.The accuracy of calculated DFIG’s controllable regions,and the effectiveness of proposed control scheme for STATCOM as well as the feasibility of respective capacity matching method are validated by the simulation results.