Comparison of the energy performance of novel dual-temperature cooling systems: From field testing to simulations
Zixu Yang,Naini Zhao,Hongli Sun,Hengxin Zhao,Yifan Wu,Mengfan Duan,Borong Lin
DOI: https://doi.org/10.1016/j.jobe.2023.106920
IF: 7.144
2023-01-01
Journal of Building Engineering
Abstract:Air conditioners (AC) face the challenge of low energy efficiency in field operation. Considering that the performance of dual-temperature systems remains unexplored, especially in different climate zones, an AC with a fiat heat pipe and different temperature controls was tested in an experimental chamber. The energy efficiency increased by 14% compared to that of an AC with a dehumidification mode. Furthermore, three novel systems that optimize the dual-temperature cooling process are proposed. These include an AC with a twin-cylinder compressor, AC with medium/low-pressure ejectors, and AC with high/low-pressure ejectors. The performance of these ACs was analyzed under different conditions. The maximum EER of the four ACs was 9.13, 9.91, 9.54, and 10.68, respectively, for an evaporation temperature of 10 degrees C and different condensation temperatures and part-load ratios. The nominal EER of the three dual-temperature systems increased by 9.4, 6.8, and 19.7%, respectively, with respect to the conventional system. The seasonal energy efficiency ratio of the three dual-temperature systems increased by approximately 5.8-18.8%, 6.3-19.9%, 6.0-18.8%, and 3.9-17.6% in four different climate zones, respectively. Our results indicate that the twin-cylinder compressor system has the highest po-tential for applications in high-efficiency cooling systems.