Simulation of the Low-temperature Hot Water Radiant Heating System with PCM Wall

Guna-yu SHI,Yan-shun YU
DOI: https://doi.org/10.3969/j.issn.1673-7237.2010.09.018
2010-01-01
Abstract:Aimed at the problems about low-temperature radiant floor heating system on application,a new system of low-temperature hot water radiant heating with PCM wall is presented,and its working principle and advantages are introduced.Based on the analysis of heat transfer of the PCM wall,a heat transfer model of thermal charging and discharging processes is established.Moreover,a 4-day continuous simulation of the cyclic charging and discharging performance for a certain PCM wall is performed by FLUENT software.The results show that the maximum and minimum temperatures are 24.8℃ and 22.8℃,23.7℃ and 22.5℃,and the maximum and minimum heat flux are 81W/m2 and 65W/m2,56W/m2 and 52W/m2 for the left and right side wall surface,respectively,during the cyclic thermal charging and discharging processes of the asymmetric PCM wall.These conclusions provide theoretical foundation for the application of the low-temperature hot water radiant heating system with PCM wall.
What problem does this paper attempt to address?