Reliability Evaluation Of Hybrid Ac/Dc Power Systems
Haitao Liu,Lin Cheng,Yuanzhang Sun,Wangqi Zheng
DOI: https://doi.org/10.3321/j.issn:1000-3673.2004.23.006
2004-01-01
Abstract:With large transmission capacity, a good, many components and high failure rate, HVDC systems have a significant impact on the reliability of power systems. With increasing applications of HVDC systems, it is necessary to research the reliability impact of incorporating an HVDC link in a power system.This paper presents an analytical method to analyze the logical relationship of the components in the HVDC system, establishes an equivalent model of HVDC systems, which is embedded in the reliability evaluation of generation and transmission power systems. The model, the algorithm and. the indices of the AC/DC power system reliability evaluation are presented. Based on the HVDC system configurations and characteristics, using fault tree analysis (FTA), the fault result of HVDC systems is divided, into three kinds: monopolar total outage, bipolar total outage and capacity reduction. Frequency and duration (FD) technique is adopted to obtain a multi-state model of HVDC systems. The effect of DC control measures is also considered in the power system state analysis.A 500kV AC/DC system is evaluated with the presented algorithm and software. The evaluation result shows that HVDC systems have a major effect on the evaluation result, and the developed algorithm and software is feasible and valid.