Design and Experimental Study of a Novel Residential Air Cooled Air-conditioning System for Independent Temperature and Humidity Control

Han Xing,Zhang Xu,Liu Jintao,Gao Siyun,Kang Yue
DOI: https://doi.org/10.3969/j.issn.0253-4339.2011.02.001
2011-01-01
Abstract:Based on the weather conditions in hot and humid area,and present problems of house air-conditioners in this region,a novel residential temperature-humidity independent control air-conditioner was designed to remove the indoor sensible heat load and latent heat load separately,which could enhance the indoor thermal comfort and energy efficiency.The experiments were carried out in the enthalpy difference lab and its SEER(3.932) and the influence of five factors based on orthogonal method,including outdoor air temperature,indoor air temperature,indoor air humidity,compressor frequency,and refrigerant distribution ratio in the air-side evaporator.Further,the impacts of the latter two factors were investigated at outdoor air temperature 34℃,indoor air temperature 26℃ and indoor relative humidity 55%.The results showed that the dehumidification capacity ranged from 0 to 4.02kg/ h,the changing ratio against compressor frequency was 0.07~0.08(kg/h)/Hz,and the changing ratio against air-side evaporator refrigerant ratio was 0.65~0.8kg/h/(10%);the EER ranged from 2.71 to 4.57,the changing ratio against compressor frequency was-0.033~-0.046/Hz,and the changing ratio against air-side evaporator refrigerant ratio was-0.12~-0.17/(10%);the refrigeration capacity ranged from 6822 to 13080W,the changing ratio against compressor frequency was 118~154W/Hz,and the changing ratio against air-side evaporator refrigerant ratio was-489~-676W/(10%);
What problem does this paper attempt to address?